Single Core Double Insulated Flexible Power and Welding Cable, 0.6/1kV

Application

These cables are used for fixed power applications, can be used in power applications,such as switchboards, busbars, transformers, welding applications ,like E and electrode leads,and automotive applications for jumper leads, battery chargers.

Standard

  • AS 5000.1
  • AS1995
  • AS1125
  • AS3808

Cable Construction

CONDUCTOR Nominal 0.2mm stranded flexible plain copper wire to AS 1125
INSULATION Nitrile (NBR) Modified PVC to comply with AS3808 V90HT
INSULATION COLOUR: White
SHEATH: Nitrile (NBR) Modified PVC to comply with AS3808 V90HT
SHEATH COLOURS: Orange, Black - other colours available by request

Technical Characteristics

Single Core Double Insulated Flexible Power and Welding Cable

CONDUCTOR SIZE MM2 ELECTRICAL
RESISTANCE
@20.C
CURRENT RAT`ING' AMPS 2 SINGLE CORES VOLTAGE OROP MV 1AM AT MAX OPERAT'ING TEMPERATURE
MM2 OHM/KM SINGLE PHASE THREE PHASE
10 1.910 69 4.45 3.86
16 1.210 92 2.80 2.43
25 0.780 125 1.78 1.54
35 0.554 155 1.29 1.12
50 0.386 185 0.96 0.83
70 0.272 240 0.62 0.59
95 0.206 295 0.51 0.44
120 0.161 345 0.41 0.36

Cable Parameter

CONDUCTOR SIZE NO.OF CORES CONDUCTOR NO./ OD NOMINAL
INSULATION THICKNESS
NOMINAL
SHEATH THICKNESS
NOMINAL O.D. APPROX.CABLE
WEIGHT
MM2   MM MM MM MM KG/100M
10 1.0 322/0.2 1.0 1.4 9.1 14.42
16 1.0 511/0.2 1.0 1.4 10.1 20.16
25 1.2 784/0.2 1.2 1.4 11.8 29.14
35 1.2 1120/0.2 1.2 1.4 13.1 38.96
50 1.4 1568/0.2 1.4 1.4 14.9 52.84
70 1.4 2240/0.2 1.4 1.5 17.0 72.34
95 1.6 3040/0.2 1.6 1.5 19.3 96.18
120 1.6 3800/0.2 1.6 1.6 20.8 117.86